Specifications

1. Overview

APS-6RF Instruction PN 50893:B 7/20/00

9

Specifications

The APS-6RF is compatible with the Sensiscan 2000, and Sensiscan 200
control panels. Specifications for the APS-6RF are:

Table 2 APS-6RF Specifications

Electrical Specifications

AC Primary Input Power
Wire Size: #14 AWG with
600 VAC insulation

120 VAC, 60 Hz, 2.5 A
240 VAC, 50 Hz, 1.2 A

24 VDC Secondary Input Power
(lead-acid batteries only)

Current draw with AC power loss
25 mA DC standby current
16 mA DC standby current (with AC fail delay
operating)
6 amps maximum alarm current

Use these values in battery calculations for Fire Alarm Control Panel
Note: Batteries are charged by the system power supply.

24 VDC output power
Circuit 1
Circuit 2
Circuit 3

Total 6 A (4 A continuous)
3 A @24 VDC power-limited (+10, –15%)
3 A @24 VDC power-limited (+10, –15%)
6 A @24 VDC non power-limited (+10, –15%)

Fuses
F1 (AC supervision)
F2 (battery supervision)

250 VAC, 4A, 3 AG, slow blow
32 VAC, 10 A, 3 AG, slow blow

Trouble supervision bus
J3 output
J4 input
Note: J3 and J4 can be
interchanged.

Form A contact (open collector)
Form A contact (open collector)

Loss of AC Indication

Immediate indication (default)
8 or 16 hour delay

Mechanical Specifications

Size of APS-6RF in enclosure

6.09 in. x 4.23 in. x 2.92 in.

Cabinets for mounting

CAB-A3F or CAB-B3F, using CHS-4F
chassis, for Sensiscan 2000 control panel.

Sensiscan 200 can mount one APS-6RF.

Note: An optional module (such as an IC-4F) without an expansion card can
mount above an APS-6RF in a CHS-4F and a Sensiscan 200.