Section 3: mounting, 1 indicator preparation, Indicator preparation – Fire-Lite LCD-80FC Remote Fire Indicator User Manual

Page 11

Advertising
background image

LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

11

Section 3: Mounting

3.1 Indicator Preparation

The LCD-80FC Indicator can be surface mounted in a three-gang electrical box such as the P/N
SBB-3 (2.75" depth) or semi-flush mounted in a three-gang electrical box, P/N 10103 or equiva-
lent, with a minimum depth of 2-3/16". The LCD-80FC Indicator can also be mounted in three
gangable electrical switch boxes connected together. Select and remove the appropriate knock-
out(s), pull the necessary wires through the knockouts and mount the box in or on the wall depend-
ing on the type of installation desired. Be certain that power is not applied to the wiring during the
installation procedure.

To mount the LCD-80FC Indicator in an electrical box, the trim ring must first be removed. The
trim ring is held in place by two screws inserted through the top and bottom edge as illustrated in
Figure 3.1. Removal of the trim ring will expose a metal flange with mounting holes. Refer to
“Hardware and Backboxes” on page 12.

NOTE: To ensure static protection, all enclosures, including the LCD-80FC electrical box, must
be connected to earth ground! Never use the shield for grounding purposes.

Screw

Screw

L

CD-8

0

F

can

ad

a.

wm

f

Figure 3.1 Trim Ring Removal