Surface Mount Backbox

Mounting

3.3 Surface Mount Backbox

Remove the plug-in terminal blocks from the LCD-80FC circuit board. Connect the EIA-485 and
power wiring into the terminal block positions illustrated in Sections 4.1 and 4.2. Plug the terminal
blocks back into the P2 and P1 connectors on the back of the indicator circuit board. Set DIP
switch SW1 for the desired options. Refer to Figure 2.2 on page 9.

Carefully insert the LCD-80FC into the three-gang electrical box and attach it using the four
mounting holes on the LCD-80FC flange and the four screws provided for this purpose. Replace
the trim ring and secure with the two screws which were previously loosened. Do not overtighten.

Local

Silence

Lamp

Test

Hold 3 sec.

LCD-80FC flange

Mounting holes (4)

The LCD-80FC can be surface mounted in a
three-gang electrical box, P/N SBB-3 or
equivalent, with a minimum depth of 2.75".

LCD-80FC

Three-gang surface box P/N SBB-3

flange

EIA-485 and power wiring

LCD

80

fc

flg

.w

mf

Sbb

-3.w

m

f

L

cd4

0b

o

x.

w

m

f

Figure 3.5 Surface Mounting