2 alarm, 3 supervisory, 4 trouble – Fire-Lite LCD-80FC Remote Fire Indicator User Manual

Page 24: 5 alarm silenced

Advertising
background image

24

LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Operation

LED Indicators

6.3.2 Alarm

This is a red LED that turns on steady when one or more fire alarms occur. The Alarm LED turns
off when the FACP Reset switch is pressed.

6.3.3 Supervisory

This is a yellow LED that turns on steady when one or more supervisory conditions occur, such as
a sprinkler valve tamper condition. It turns off when the FACP Reset switch is pressed.

6.3.4 Trouble

This is a yellow LED that turns on steady when one or more trouble conditions occur. The LED
turns off when all trouble conditions are cleared. This LED will also illuminate if the microproces-
sor watchdog circuit within the LCD-80FC is activated.

6.3.5 Alarm Silenced

This is a yellow LED that turns on when the FACP Silence switch is pressed to turn off the Notifi-
cation Appliance Circuits. The LED turns off when the NACs turn back on or when the alarm con-
dition is cleared and the FACP is reset back to a normal condition.