Section 5: eia-485 shield termination, 1 shield not in conduit, Shield not in conduit – Fire-Lite LCD-80FC Remote Fire Indicator User Manual

Page 20

Advertising
background image

20

LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Section 5: EIA-485 Shield Termination

The EIA-485 circuit must be wired using a twisted, shielded pair cable with a characteristic imped-
ance of 120 ohms (+/- 20%). Do not run cable adjacent to or in the same conduit as 120 VAC ser-
vice, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25
V

RMS

, motor control circuits or SCR power circuits.

5.1 Shield Not in Conduit

The EIA-485 line allows the FACP to communicate with the LCD-80FC Indicator. The shield for
the EIA-485 line must be connected to earth ground at the FACP but must be left floating (no con-
nection) at the indicator if it is the first or only device on the EIA-485 line. If a second indicator is
connected, the shield leaving the first indicator must be left floating. The shield entering the sec-
ond indicator must be connected to the three-gang box or Earth Ground terminal (P2-7) on the sec-
ond indicator. If additional indicators are connected, the shield leaving each enclosure must be left
floating and the shield entering each must be connected to the three-gang box or the Earth Ground
terminal (P2-7) on the indicator.

NOTE: To ensure static (ESD - electrostatic discharge) protection, all enclosures, including the
LCD-80FC electrical box, must be connected to earth ground! Never use the EIA-485 shield for
this purpose. The EIA-485 shield is for radiated noise emission protection (RFI, EMI). Refer to the
following figures for details on EIA-485 shield termination.

Connect the drain wire to the outside of the

FACP cabinet via a BX-type connector.

Shield Drain Wire

FACP Backbox

(+) EIA-485

(-) EIA-485

FACP

fd

u8

0sh

l.w

mf

FACP

indicator

indicator

indicator

Figure 5.1 EIA-485 Without Conduit

shield

EIA-485 Loop

not in conduit

Advertising