2 eia-485 connections – Fire-Lite LCD-80F Remote LCD Annunciator User Manual

Page 25

Advertising
background image

Electrical Connections

EIA-485 Connections

25

Document 51338 Rev. B 08/24/05 P/N 51338:B

4.2

EIA-485 Connections

Notes:

1. All connections are power-limited and supervised
2. A maximum of 32 LCD-80F annunciators may be connected to

this circuit

3. 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm

2

)

between the FACP and first LCD-80F, between each LCD-80F

and return to the FACP from last LCD-80F

4. Use overall foil/braided-shielded twisted pair cable suitable for

EIA-485 applications (refer to “EIA-485 Shield Termination” on

page 26, for shield termination information). Six conductor

overall shielded wire may be used for the four EIA-485 wires

and the two power wires. It is, however, strongly recommended

that the power and communication wires be separate whenever

possible

5. Ferrite Core P/N FBD-1 is required to meet FCC Part 15 require-

ments if the EIA-485 wiring is not in conduit

6. The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA

maximum

7. The LCD-80F annunciator has resistors built into the circuit

board at the In (Terminals 2 & 4) and the Out (Terminals 1 & 3)

for impedance matching. There is no need for the installer to add

impedance matching resistors

8. Enable FACP communication with the LCD-80F in the FACP

programming if appropriate (refer to FACP manual)

4 3 2 1

7 6 5 4 3 2 1

1 2 3 4 5 6 7 8

Figure 4-2:

EIA-485 Connection

P2

P1

+ EIA-485 OUT

+ EIA-485 IN

- EIA-485 OUT

- EIA-485 IN

in from FACP

Out to next LCD-80F or return to

host FACP if last or only annuncia-

tor on the line

Ferrite Core P/N FBD-1 is required (see note 5)

F

D

U

80B

ds

cdr

LCD-80F