EIA-485 Shield Termination

Shield in Full Conduit

28

Document 51338 Rev. B 08/24/05 P/N 51338:B

5.2

Shield in Full Conduit

The EIA-485 line allows the FACP to communicate with the LCD-80F
Annunciator. The shield for the EIA-485 line must be connected to earth
ground at the FACP (both exiting and entering the FACP) but must be
left floating (no connection) at the annunciator if it is the first or only
device on the EIA-485 line. If a second annunciator is connected, the
shield leaving the first annunciator must be floating. The shield entering
the second annunciator must be connected to the Earth Ground terminal
(P2-7) on the second annunciator. If additional annunciators are con-
nected, the shield leaving each annunciator must be left floating and the
shield entering the following unit must be connected to the Earth
Ground terminal (P2-7) on the annunciator.

Caution! Do not allow the floating shield end (no connection) to contact
the conduit. The floating end should be insulated from earth ground.

Notes:

1. Power-limited 24 VDC power may be run in the same conduit as the

EIA-485 wiring

2. Twisted, shielded wire is recommended for the EIA-485 communica-

tions loop

3. Each electrical backbox is connected to earth ground via the conduit

4. Shield is connected to the FACP cabinet (earth ground) leaving and

entering the FACP

EIA-485 Loop
in Conduit

Shield

Earth Ground

Earth Ground

Figure 5-2:

EIA-485 In Conduit

LCD-80F Box

LCD-80F

P1-2 (+)

EIA-485 (IN)

P1-4 (-)

EIA-485 (IN)

P2-7 Earth

Ground (IN)

Connect the shield drain wire to the Earth Ground
Terminal on the Annunciator

Shield Drain Wire