LCD-80F Annunciator

Components & Wiring

9

Document 51338 Rev. B 08/24/05 P/N 51338:B

4 3 2 1

7 6 5 4 3 2 1

1 2 3 4 5 6 7 8

Figure 1-2:

Wiring to Terminals

Terminal Block

replacement

P/N 02108

P2

P1

Terminal Block

replacement

P/N 02109

EIA-485 OUT

EIA-485 IN

EIA-485 OUT

EIA-485 IN

no connection

+24 VDC IN

+24 VDC OUT

-24 VDC IN

-24 VDC OUT

Earth Ground Option

Note: These connections must be power-limited and the +24 VDC nom-
inal power input must be filtered and nonresettable.

Refer to illustrations on the following page for LCD-80F connections to
the MS-9200UD and MS-9600.

MS-9200UD

(TB8)

MS-9600

(TB7)

LCD-80F

(P1 Connector)

Terminal 2 IN (+)

Terminal 5 IN (+)

Terminal 1 OUT (+)

Terminal 4 IN (-)

Terminal 6 IN (-)

Terminal 3 OUT (-)

Terminal 1 OUT (+)

Terminal 7 OUT (+)

Terminal 2 IN (+)

Terminal 3 OUT (-)

Terminal 8 OUT (-)

Terminal 4 IN (-)

Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 64.3 mA
Trouble Condition: 64.3 mA
Alarm: 64.3 mA
AC Fail (not backlit): 25 mA

Side view

FD

U

80B

ds

.cdr

in from FACP

EIA-485 Terminals

Terminals Out to next

LCD-80F

or back to

FACP if this is last or

only device on the line.

+

-

+

-