1.4 MEASURING

(OVERVOLTAGE) CATEGORIES DEFINITIONS

The norm IEC/EN61010-1: Safety requirements for electrical equipment for measurement,
control and laboratory use, Part 1: General requirements, defines what measuring
category, usually called overvoltage category, is. On paragraph 6.7.4: Measuring circuits, it
says:

(OMISSIS)

circuits are divided into the following measurement categories:

Measurement category IV is for measurements performed at the source of the low-

voltage installation

Examples are electricity meters and measurements on primary overcurrent protection
devices and ripple control units

Measurement category III is for measurements performed in the building installation

Examples are measurements on distribution boards, circuit breakers, wiring, including
cables, bus-bars, junction boxes, switches, socket-outlets in the fixed installation, and
equipment for industrial use and some other equipment, for example, stationary
motors with permanent connection to fixed installation

Measurement category II is for measurements performed on circuits directly

connected to the low voltage installation

Examples are measurements on household appliances, portable tools and similar
equipment

Measurement category I is for measurements performed on circuits not directly

connected to MAINS

Examples are measurements on circuits not derived from MAINS, and specially
protected (internal) MAINS-derived circuits. In the latter case, transient stresses are
variable; for that reason, the norm requires that the transient withstand capability of the
equipment is made known to the user