Mpp300 – HT instruments MPP300 User Manual

Page 14

Advertising
background image

MPP300

EN - 12

17. The display of SOLAR I-V will show the values of the

general electrical parameters of the system being
measured

In particular, in this screen:
Pdc = General dc power (sum of the string powers)
Pac = ac power (if single-phase) or sum of the ac powers (if
three-phase)

We recommend checking that the values of the electrical
parameters (Pnom, Pdc, Pac) and of the ac performance
(

ac) are consistent with the system being measured (e.g.:

ac > 1 is not physically acceptable)

15/05/10 15:34:26

P R p

- - -

I r r

- - -

W / m 2

P n o m 3 . 5 0 0

k W

T c

- - -

° C

T e

- - -

° C

P d c

3 . 1 2 5

k W

P a c

2 . 9 6 0

k W

n d c

- - -

n a c

0 . 9 5

G O – s t a r t r e c

Select

M P P

18.

On SOLAR I-V, press key (

) to access the second

screen which contains the values of the output DC
parameters of the strings according to the number of DC
inputs set (see the User Manual of SOLAR I-V)

In particular, in this screen:
Vdcx = dc voltage of string x.
Idcx = dc current of string x.
Pdx = dc power of string x.

We recommend checking that the values of the electrical
parameters (Vdc, Idc, Pdc) are consistent with the system
being measured

15/05/10 15:34:26

V d c 1

4 6 0 . 1

k W

V d c 2 4 6 1 . 4

V

V d c 3

4 6 2 . 5

A

I d c 1

2 . 2 5

A

I d c 2

2 . 3 1

A

I d c 3

2 . 2 1

A

P d c 1

1 . 0 3 5

k W

P d c 2

1 . 0 6 6

k W

P d c 3

1 . 0 2 4

k W

G O – s t a r t r e c

Select

M P P

19. On SOLAR I-V, press key (

) to access the third screen

which contains the values of the electrical parameters on
the AC side of the inverter, consistently with the settings
made (see – SOLAR I-V user’s manual, single-phase,
three-phase 4 wires).

In particular, in this screen:
Vacxy = ac voltage between Phase and Neutral (if single-
phase) or between Phases x and y (if three-phase)
Iacx = ac current of phase x
Pacx = ac power of phase x

We recommend checking that the values of the electrical
parameters (Vac, Iac, Pac) are consistent with the system
being measured

15/05/10 15:34:26

V a c 1 2 4 0 1 . 4

V

V a c 2 3 4 0 1 . 1

V

V a c 3 1 4 0 0 . 1

V

I a c 1

4 . 2 6

A

I a c 2

4 . 2 6

A

I a c 3

4 . 2 7

A

P a c 1

9 8 7

W

P a c 2

9 8 6

W

P a c 3

9 8 5

W

G O – s t a r t r e c

Select

M P P

E x a m p l e o f a s c r e e n f o r
P V s y s t e m s w i t h t h r e e -
p h a s e o u t p u t

20. Keeping the three instruments near each other (max distance

approx. 1m), press the GO/STOP key on SOLAR I-V to start
testing. Consequently:

 The display of SOLAR I-V shows the message “Rec. start

waiting

 The display of SOLAR-02 shows the message “HOLD” and

the time, expressed in seconds, remaining before the
recording is started

 On MPP300, the STATUS LED turns on green (not flashing)

15/05/10 15:34:26

P R p

- - -

I r r

- - -

W / m 2

P n o m 3 . 5 0 0

k W

T c

- - -

° C

T e

- - -

° C

P d c

3 . 1 2 5

k W

P a c

2 . 9 6 0

k W

n d c

- - -

n a c

0 . 9 5

R e c . S t a r t W a i t i n g

Select

M P P