Operating instructions – KYORITSU 1109S User Manual

Page 13

Advertising
background image

̶ 11 ̶

6. Operating Instructions

6-1. Preparation

● Make certain that the batteries are installed into the battery case with

polarity in correct position. Also, make sure that the fuses are properly

installed.

● The test leads are safety designed, but make sure that they are

securely connected to the instrument before use.

● Check that the meter pointer lines up with the "0" mark on the left end

of the scale. If it is off zero, rotate the zero adjust screw to bring the

pointer to the zero position. Accurate measurements cannot be made

without the zero adjustment.

● With the range selector switch at the x 1Ω range position and the

test leads connected to the + and −COM terminals of the instrument,

short the test leads together. If the pointer does not deflect at all, the

probable cause is the absence of batteries or the blown fuse. [Refer

to section 7]

● With the range selector switch set to the x1Ω range position, short

the tips of the test leads together. Turn the ohm zero adjust knob and

make certain that the meter pointer moves to the "0" mark on the

right end of the ohm scale. If not, the battery voltage is insufficient.

Replace all of the 1.5V batteries (R6P, SUM-3 or equivalent). Refer to

section 7 for battery replacement.

● With the range selector switch at the x10kΩ position short the tips of

the test leads together. Then, turn the zero adjust knob clock-wise

and make certain that the meter pointer moves to the "0" mark on the

right end of the ohm scale. If not, the battery voltage is insufficient.

Replace the 9V battery (6F22, 006P or equivalent).

● Select a measuring range suitable for the circuit being tested. When

in doubt as to the maximum voltage or curre'1t expected, make sure

to start with the• highest voltage or current range of the instrument.