Danger, 5 operating time – KYORITSU 5410 User Manual

Page 20

Advertising
background image

● Earth – Line
Connect the “PRIMARY” of the Connector Block to Earth, and the
“SECONDARY” of the Connector Block to Line of the load of RCD.










DANGER

Extra caution should be taken when applying current to EARTH for
tests since the other RCDs (see Fig.10) may operate and damage the
devices connected to the instrument and cause accidents.

8-5 Operating time

Tripping time is the time needed by the RCD to trip at a rated residual
operating current of IΔn. The standard values of tripping time are defined
by IEC 61009 and IEC 61008 are listed in the table below for IΔn and
5IΔn.

Type of RCD

IΔn(x1) 5IΔn(x5)

General(G) 300ms

max allowed value

40ms

max allowed value

500ms

max allowed value

150ms

max allowed value

Selective(S)

130ms

min allowed value

50ms

min allowed value

KEW 5410

Leakage

LINE

NEUTRAL

EARTH

RCD(A)

RCD(B)

Leakage currents may flow to RCD (A),
which is installed in the power supply of the
RCD (B) under test, when current flows to
the EARTH; so RCD (A) may trip as well.

current

Connection using Earth

POWER

RED

LOAD

Test lead with

alligator clip

Fig.9

Fig.10