● Operating error

Operating error (B) is an error obtained under the nominal operating
conditions, and calculated with the intrinsic error (A), which is an error
of the instrument used, and the error (En) due to variations.

B = ± ( |A| + 1.15 x √E

1

² + E

2

² + E

3

² + E

5

²+ E

8

² )

A : Intrinsic error
E

1

: Variation due to changing the position

E

2

: Variation due to changing the supply voltage

E

3

: Variation due to temperature

E

5

: Variation due to the resistance of Probe *

E

8

: Influence by the variation in System Voltage

*Probe = auxiliary Earth electrode to be used for the

sampling of electric potentials during measurements

IΔn Probe

resistance

15mA

Less than 200Ω

30mA

Less than 100Ω

50/100/200/500mA

Less than 20Ω


KEW5410 Max Operating Error (IEC61557)

Range

Max Operating Error

test current 0% ~ +10%

x 5

time measurement ±10%
test current 0% ~ +10%

x 1

time measurement ±10%

x 1/2

test current -10% ~ 0%

AUTO RAMP (mA)

±6%


7