Specification – KYORITSU 5410 User Manual

Page 7

Advertising
background image

4. Specification


Measuring range and accuracy

(23ºC±5ºC, relative humidity 75% or less)

Range

Rated

Voltage

Test current

IΔn

Measuring

range

Accuracy

Trip Time

±(1%rdg+3dgt)

x 5

10 / 30 / 50

/ 100mA

Testing time

0ms ~ 200ms

Test Current

+2% ~ +8%

Trip Time

±(1%rdg+3dgt)

x 1

Testing time

0ms ~ 2000ms

Test Current

+2% ~ +8%

Trip Time

±(1%rdg+3dgt)

x 1 / 2

10 / 30 / 50

/ 100 / 200

/ 500mA

Testing time

0ms ~ 2000ms

Test Current

-8% ~ -2%

AUTO

RAMP

(mA)

100V±10%

200V+32%

/-10%

400V±10%

50 / 60Hz

10 / 30 / 50

/ 100 / 200

/ 500mA

40%~ 110% of IΔn

(goes up by 5%)

Testing time

300ms x 15steps

Test Current
at each step

-4% ~ +4%

* Only the RCD type G (without trip out time-delay) can be tested at

Auto Ramp Test; type S (time-delay) cannot be tested.


Voltage Measurement

Measuring range

Accuracy

80V ~ 450V

50 / 60Hz

±(2%rdg+4dgt)

Applied standards

: IEC61010-1 Measurement Category

CAT.III 300V / CAT.II 400V,

Pollution

degree

2

IEC61010-031
IEC61557-1,

6

IEC60529 IP54

5