Set-up: set up range – KYORITSU 6305 Quick Manual User Manual

Page 10

Advertising
background image

9 −

KEW6305

KEW6305

Set-up:

SET UP

Range

4. Set-up:

SET UP

Range

Set the Function switch to

SET UP

Range for making various settings.

Settings listed below can be changed. (27 items in total)
List of setting items

Setting Setting no./ item

Symbol

Details

Basic

setting

01 Wiring system

1P2W(1ch)/ 1P2W(2ch)/ 1P2W(3ch)/

1P3W/ 3P3W/ 3P3W3A/ 3P4W

02 Voltage range

150/ 300/ 600V

03 Clamp sensor

50/ 100/ 200/ 500/ 1000/ 3000A type

04 Current range

-

03

Sensor Range

50A

1/5/10/25/50A/AUTO

100A 2/10/20/50/100A/AUTO
200A 4/20/40/100/200A/AUTO
500A 10/50/100/250/500A/AUTO

1000A 20/100/200/500/1000A/AUTO
3000A 300/1000/3000A

05 VT ratio

0.01 - 9999.99 (can be set by 0.01)

06 CT ratio

0.01 - 9999.99 (can be set by 0.01)

Time&

Buzzer

07 Date and time

Year:Month:Day:Hour:Minute:Second

08 Buzzer

ON / OFF

Measure-

ment

09 Recording interval

1/ 2/ 5/ 10/ 15/ 20/ 30 sec./

1/ 2/ 5/ 10/ 15/ 20/ 30 min./ 1 hour

10 Specific time period

rec. or endless rec.

ON: Specifying start/ stop time

(repeatedly recorded)

OFF : Record the data continuously

11

*1

Time period setting

Time setting

Start and stop time

(Year:Month:Day:Hour:Minute:Second)

12

*1

Time period setting

Date setting

Year:Month:Day:Hour:Minute:Second

13

*2

Start of continuous

measurement

Year:Month:Day:Hour:Minute:Second

14

*2

End of continuous

measurement

Year:Month:Day:Hour:Minute:Second

15 Target demand

Value : 0.1 - 999.9

Unit: W/kW/MW/GW/VA/kVA/MVA/GVA

16 Demand measure-

ment cycle

NO/ 10/ 15/ 30 min

* Demand measurement will not be

performed when “NO” has been

selected.

17 Demand warning

cycle

1/2/5 min. when measurement cycle is

10or15 min., 1/2/5/10/15 min. when

measurement cycle is 30 min.

*1 : Setting 11& 12 can be changed only when Setting 10 has been set to “ON”.

*2 : Setting 13& 14 can be changed only when Setting 10 has been set to “OFF”.