TM 40/40M, Rev (6) July 2013

Connecting the Detector

27

4

Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5
flameproof gland to assemble the cable / conduit to the detector.

Figure 8: Detector with Cover Removed

5

Connect the wires to the required terminals on the Terminal Board
according to the wiring diagram (Figure 8) and Table 15.

6

Connect the grounding (earth) wire to the ground (earth) screw outside
the detector (Earth Terminal). The detector must be well grounded to
earth ground.

7

Verify the wiring. Improper wiring may damage the detector.

8

Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the
back cover (Figure 8).

9

Place and secure the detector’s back cover by screwing the three (3)
socket-head-screws in the Cover Bolts (Figure 5).

Earth
Terminal

Terminal

Chamber

Terminals

Internal Earth

Terminal

Detector Holding
Screw
Conduit / Cable

Inlet