Electrical specifications, Outputs, Table 21: electrical specifications – Spectrex 40/40M Multi IR Flame Detector User Manual

Page 56: A.2 electrical specifications, A.3 outputs

Advertising
background image

Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

44

Outputs

A.2

Electrical Specifications

Operating Voltage: 18-32 VDC

Power Consumption: Table 21

Table 21: Electrical Specifications

Operating
Voltage

Status

All
Outputs

Without
0-20mA

Power
Consumption

(Max. 24VDC)

Normal

1.61W

1.56W

Normal when Heater On

2.28W

2.16W

Alarm

2.64W

2.28W

Alarm when Heater On

3.24W

2.88W

Maximum Current
(Max. 24VDC)

Normal

70mA

65mA

Normal when Heater On

95mA

90mA

Alarm

110mA

95mA

Alarm when Heater On

135mA

120mA

Power
Consumption

(Max. 18-32VDC)

Normal

1.95W

1.85W

Normal when Heater On

2.56W

2.45W

Alarm

3.04W

2.56W

Alarm when Heater On

3.68W

3.2W

Maximum Current
(18-32VDC)

Normal

90mA

85mA

Normal when Heater On

105mA

100mA

Alarm

130mA

115mA

Alarm when Heater On

160mA

145mA

Electrical Input Protection The input circuit is protected against

voltage-reversed polarity, voltage transients,
surges and spikes according to MIL-STD-
1275B

A.3

Outputs

Electrical
Interface

There are five output-wiring options. These options must
be defined at the factory per the customer order and

cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 49

for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The
wiring arrangement is identified on the detector by the

part number (see Model and Types on page 2).

Option 1: Power, RS-485, 0-20mA (Sink), Fault I

Relay (N.C), Alarm Relay, (N.O) (see Figure 8).