Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

34

Safety Precautions

3.2

Safety Precautions

After powering-up, the detector requires almost no attention in order to
function properly, but the following should be noted:

Follow the instructions in this guide and refer to the drawings and

specifications.

Do not expose the detector to radiation of any kind unless required for

testing purposes.

Do not open the detector housing, while power is applied.

Do not open the electronic compartment. This part should be kept closed

at all times and only opened in the factory. Opening the electronic
component side invalidates the warranty.

You should only access the wiring compartment to wire or remove the

detector or access RS485 terminals for maintenance.

Disconnect or disable external devices, such as automatic extinguishing

systems before carrying out any maintenance.

3.2.1 Default Functions Settings

Table 18 lists the default function configuration supplied with the detector.

Table 18: Default Function Values

Function

Value

Notes

Sensitivity

30

Alarm Delay

A

Antiflare

Alarm Latch

No

Auxiliary Relay

No

In wiring options 1, 2, 3 the Auxiliary Relay
is not available. This function is not used.

Automatic BIT

Yes

Alarm BIT

No

Auxiliary BIT

No

In wiring options 1, 2, 3 the Auxiliary Relay
is not available. This function is not used.

EOL

No

In wiring options 1, 2, 3 the Auxiliary Relay
is not available. This function is not used.

Heat Mode

Auto

Heat On

41°F

(5°C)

The detector starts heating the window for
any temperature below this value (in
degrees Celsius).

In order to change the default function use:

Mini Laptop Kit P/N 777820. Refer to manual TM777070 for

programming instructions when using the Mini Laptop Kit.

USB RS485 Harness Kit P/N 794079-5. Refer to manual TM777050

for programming instructions when using the USB RS485 Harness
Kit.

HART protocol, refer to Manual TM777030 for instructions.