Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 26

Advertising
background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

18

E. Electrical outputs

Dry Contact Relays:

Table 9: Contact Ratings

Relay
Name

Type

Normal
position

Maximum Ratings

Alarm

SPDT N.O. N.C. 2A at 30VDC or 0.5A at 250 VAC

Accessory SPST N.O.

5A at 30VDC or 250 VAC

Fault

SPST N.C.

5A at 30VDC or 250 VAC

4-20mA Current Output:

Terminals 11 and 12:

STATE

Output

FAULT

0 + 0.5mA

BIT FAULT

2mA±10%

NORMAL

5mA±10%

WARNING 10mA±5%
ALARM

15mA±5%

Communication Network:

The detector is equipped with an RS-485 communication link that can
be used in installations with computerized controllers.

The communicator protocol is compatible with the Modbus
communicator protocol.

o

This protocol is a standard and widely used.

o

It enables continuous communication between a single standard
Modbus controller (Master device) and a serial Network of up to
247 detectors.

o

It enables connection between different types of Spectrex detectors
or other

o

Modbus devices to the same Network.


Advertising