Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 44

Advertising
background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

36

8.5 Maintenance Records

It is recommended to record maintenance operations performed on a detector in a
system log-book. The record should include information, which identifies the unit,
the installation date, contractor, and entries for every maintenance operation
performed including the description of the operation, date and personnel ID. If a
unit is sent to the manufacturer or distributor for service, a copy of the
Maintenance records should accompany it.

8.6 Troubleshooting

8.6.1 Fault Indication

1 Check power supply for correct voltage, polarity and wiring.

2 Check detector window and reflector for cleanliness. If necessary clean the

window as indicated in paragraph 8.3 and repeat the test.

3 Disconnect the power supply to the system and check the detector's internal

wiring.

4 Reconnect power supply and wait approximately 60 seconds. Repeat the test.

If the indication LED is still blinking, the unit requires service.

8.6.2 False Alarm or Warning Indication


1 Disconnect the power supply from the system and check internal wiring.

2 Reconnect power supply and wait approximately 60 seconds. If indication

remains, the unit requires service.