Appendix a - wire selection tables – Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 45

Advertising
background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

37

Appendix A - Wire Selection Tables


General Instructions For Electrical Wiring

1. Refer to Table 12 to determine the required wire gauge for general wiring,

such as relay wiring. Calculate the permitted voltage fall with respect to
loads current, wire gauge and length of wires.

2. Refer to Table 13 to select wire gauge for power supply wires. DO NOT

connect any circuit or load to detectors’ supply inputs.

Table 12: Maximum DC resistance at 68˚F for copper wire

AWG # mm

2

Ohm per 100 ft.

Ohm/100

meter

26 0.12

-

0.15 4.32

14.15

24 0.16

-

0.24 3.42

11.22

22

0.30 - 0.38

1.71

5.60

20

0.51 - 0.61

1.07

3.50

18

0.81 - 0.96

0.67

2.20

16

1.22 - 1.43

0.43

1.40

14

1.94 - 2.28

0.27

0.88

12

3.09 - 3.40

0.17

0.55

10

4.56 - 6.64

0.11

0.35

A. Select "Number of detectors" connected in one circuit.
B. Select "wiring length" per your installation requirements.
C. Refer to "power supply range" for voltage extreme applied.

Table 13. Wiring length in feet (meter)

No. of
Detectors

Recommended Wire Diameter

Power Supply
Range (VDC)

24

18

16

14

-

-

22-32

20

18

16

14

-

-

22-32

16

20

18

16

14

-

22-32

12

20

18

16

14

-

20-32

8 20

18

16

14

-

20-32

4

and

less

20

18 16 16 14

20-32

Feet

164

328 492 656 820

(meters)

(50)

(100) (150) (200) (250)

Max. Length from Power Supply to Last

Detector

Advertising