Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 42

Advertising
background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

34

7.4.1 Manual BIT Test

Important Note!

If the function setup “Alarm BIT” and/or “Accessory BIT” are in YES, then the
Alarm, Accessory Relay and 4-20mA Output will be activated during a manual
BIT, therefore, automatic extinguishing systems or any external devices that may
be activated during BIT must be disconnected.

1

Verify that the detector is operated properly.

2

Initiate manual BIT. After a few seconds the following occurs:

• Alarm Relay will be activated and the 4-20mA output turns to 15mA for

3 seconds (only if SW1-4 is ON).

• Accessory Relay will be activated and the 4-20mA output turns to

10mA for 3 seconds (only if SW1-5 is ON).

• The 2 LEDs should be ON.

• Fault Relay will stay active during the test.

7.5 Safety Precautions

After Powering-up, the detector requires hardly any attention in order to function
properly, but the following should be noted:

1 Follow the instructions in the manual and refer to the drawings and

specifications issued by the manufacturer.

2 Do not expose the detector to radiation of any kind unless required for testing

purposes.

3 Do not open the detector housing while power is supplied.

4 Do not touch internal parts. Interference with internal circuits may impair

detector performance and will invalidate manufacturer's Warranty.

5 Disconnect external devices, such as automatic extinguishing systems before

carrying out any maintenance.