Spectrex 20/20F - Fast UV/IR Flame Detector User Manual

Page 13

Advertising
background image

Spectrex Inc. - SharpEye

TM

UV/IR (F) Flame Detector Manual – TM756100 Rev A, July 2005

7

Other Fuels:
The Detector will react to other fuels in standard fire conditions at maximum
response time of 3 seconds.

The sensitivity range to other fuels varies according to the fuel type. Table 1
below provides the sensitivity to other fuels relative to (as a percentage of) the
sensitivity to a standard gasoline fire source.

Table 1. Response Sensitivity Ranges

Type of Fuel

% of Max. Distance at Each
Sensitivity Range

Gasoline 100%
N-Heptane 100%
Alcohol 95%

25%

JP4 75%
Kerosene 75%
Diesel Fuel

50%

Table 2: Response to Pyrotechnic Material

Material

Description

Time to Detection

RS41 Incendiary

composition

2-3

msec

M206

IR Flare composition

3-4 msec

M14 Propellant 12-41

msec

Advertising