Appendix c. mounting the “eexde approved” version – Spectrex 20/20F - Fast UV/IR Flame Detector User Manual

Page 37

Advertising
background image

Spectrex Inc. - SharpEye

TM

UV/IR (F) Flame Detector Manual – TM756100 Rev A, July 2005

31

Appendix C. Mounting the “EExde approved”
version


The EExde approved version provides an additional EExe terminal box attached
below the EExd detector and therefore allows easier access in hazardous areas
(see fig. 10). The unit is prewired to the terminals in the additional EExe terminal
section ready for field wiring connections

1. Detector Mounting
The detector may be mounted on a simple fabricated bracket, or preferably the
optional Swivel Mount, Model 20/20-003. The Swivel Mount enables the detector
to be rotated up to 40 degrees in all directions.

1.1 Swivel Mount Kit
Use the kit from the paragraph 6.5.1

1.2 Swivel installation

1 Refer to Fig. 4b and Fig. 8 Place the swivel mount in its designated location

and secure it with four (4) M6 or 1/4" screws, placed 76.2 mm. (3.0 in.) apart
on the swivel mount plate (item 6, Fig 4b).

Note

: Skip this step if the Swivel Mount is already installed. Also detector

removal for maintenance purpose does not require Swivel Mount removal.

2 Unpack the detector.

3 Place the detector, with its cable inlets pointing down, on the holding plate of

the swivel mount (Fig. 4a item 6). Secure the detector by four (4) M6 screws
with M6 spring washers from the Swivel Mount Kit using the holes. You can
use the thread on the modified cover
(Fig. 8 item 1) marked either triangle symbol (∆) or square symbol (ٱ). Use
No. 5 Hex Key for M6 screws.

4 Tighten the three locking 3/8"-24UNF screws (Fig. 4b item 4) of the swivel

mount ring until the friction in the ball joint holds the detector in its position.
Yet, still permits it to be moved by hand-applied force (Use No.5 Hex Key).

5 Point the detector towards the protected area and make certain that the view

of the area. Secure the detector in that position by tightening the locking
screws (Fig.4b item 4) of the swivel mount ring.


The detector is now correctly located and aligned and ready for connecting to the
system.

Advertising