1 The following test will simulate a real fire condition and may activate the

extinguishing system or other alarms. If this is not desired, disconnect them
before the test and reconnect after the simulation.


Follow these instructions to simulate a fire:

1 Aim the Fire Simulator towards the detector’s “Target Point” (see Fig. 14)

2 For testing, keep a distance of at least 20 inches (50cm) from the detector.

3 Press the operation button once. Fire simulation will last for 20 seconds. The

detector will send an alarm signal.

4 For another fire simulation a 20 second time lapse is required between tests.

5 Make sure the optical window is clean and keep the Fire Simulator in the

storage case when not in use.