6.7 Terminal Wiring (Figure 6)

The detector contains a terminal board labeled 1 to 7.

The following describes the function of each electrical terminal of the detectors.

Power Supply:

(Terminals 1, 2)

Input power is supplied to terminal No. 1.
The RETURN is connected to terminal No.2.

Manual Bit Activation:

(Terminal 3)

Terminal No. 3 is used for the manual BIT activation. The manual BIT is initiated
by a momentary connection of Terminal No. 3 to the power supply return line.

Alarm Relay:

(Terminals 4, 5)

The Alarm output is a change - over contact relay (SPDT)
Terminal No. 4 is the NO relay contact
Terminal No. 5 is the COMMON relate contact

Fault Relay

: (Terminals 6, 7)

The Fault output in NC SPST contact at terminals no. 6 and 7. The contacts are
closed when the detector is in its normal operational condition
Terminal No. 6 is the NO relay contact.
Terminal No. 7 is the common relay contact.

Note

To protect the dry contacts from voltage surges when connected to
reactive loads (electric motors, sirens, etc.), connect an appropriate
varistor over these contacts.