West Control Solutions N4400 User Manual

Page 28

Advertising
background image

Parameter

Message

Display

Function

Available Settings/Values

(Lower Main Display)

Setpoint Low
Limit

6

The minimum limit for setpoint
adjustment. Should be set to a
value which prevents setpoint
values causing damage to the
process.

Input Range Minimum to current
setpoint value.
Default = Input Range Min.

Motor Travel
Time

11

Time taken for valve to travel
from one end stop to the other

5secs. to 5mins.
Default = 1min.

Minimum Motor
ON Time

11

Minimum drive effort required to
initiate movement in a
stationary valve

0.0secs. to (Motor Travel Time
+ 10).
Default = 1.0sec.

Recorder Output
Scale Maximum

7

The value of the process
variable or setpoint (as
applicable) for which the
recorder output is a maximum.

1999 to 9999 (decimal point

position as per process variable
input range).
Default = Input Range Max.

Recorder Output
Scale Minimum

7

The value of the process
variable or setpoint (as
applicable) for which the
recorder output is a minimum.

1999 to 9999 (decimal point

position as per process variable
input range).
Default = Input Range Min.

Output Power
Limit

3

Limits the power level of Output
1 (used to protect the process)

0% to 100%.

Output 1 Cycle
Time

8

Limits the frequency of
operation of the output relay to
optimise relay life

0.5, 1, 2, 4, 8, 16, 32, 64, 128,
256 or 512secs.
Default = 30secs.

Output 2 Cycle
Time

8

Limits the frequency of
operation of the output relay to
optimise relay life

0.5, 1, 2, 4, 8, 16, 32, 64, 128,
256 or 512secs.
Default = 30secs.

Process High
Alarm 1 value

If Alarm 1 is a Process High
Alarm, this defines the level of
the process variable at or above
which Alarm 1 will be active
(see Figure 9-2)

Input Range Maximum to Input
Range Minimum.
Default = Input Range Max.

Process Low
Alarm 1 value

If Alarm 1 is a Process Low
Alarm, this defines the level of
the process variable at or below
which Alarm 1 will be active
(see Figure 9-2)

Input Range Minimum to Input
Range Maximum.
Default = Input Range Min.

Band Alarm 1
value

If Alarm 1 is a Band Alarm, this
defines the band of process
variable value (centred on the
setpoint) outside which the
process variable will cause the
alarm to become active (see
Figure 9-2).

±

(input span) from setpoint.

Default = 5 input units.

Page 9-3

59215-9