West Control Solutions N4400 User Manual

Page 30

Advertising
background image

Parameter

Message

Display

Function

Available Settings/Values

(Lower Main Display)

Loop Alarm Time

If ON/OFF control is selected
(i.e PB1 = 0) and Loop Alarm is
enabled, this defines the
duration of the saturation
condition after which the Loop
Alarm is activated (see
Subsection 9.3)

1sec. to 99mins. 59secs.
Default = 99mins. 59secs.

Scale Range
Decimal Point
Position

9

For linear inputs, defines the
decimal point position.

0 (xxxx)

1 (xxx.x)

2 (xx.xx)

3 (x.xxx)

Default = 1 (xxx.x)

Scale Range
Maximum

9

For linear inputs, defines the
scaled input value when the
process variable input is at its
maximum value.

1999 to 9999 (decimal point

position as defined by Scale
Range Decimal Point Position
parameter).
Default = 100.0

Scale Range
Minimum

9

For linear inputs, defines the
scaled input value when the
process variable input is at its
minimum value.

1999 to 9999 (decimal point

position as defined by Scale
Range Decimal Point Position
parameter).
Default = 0.0

Auto Pre-Tune
Enable/Disable

Determines whether the
Pre-Tune facility is activated
automatically at power-up.

OFF = disabled; On = enabled.
Default = OFF (disabled).

Manual Control
Enable/Disable

Enables/disables operator
selection of Manual Control.

OFF = disabled; On = enabled.
Default = OFF (disabled).

Communications
Write
Enable/Disable

10

Enables/disables changing of
parameter values or settings via
the RS485 Communications link

OFF = disabled;

On = enabled.

Default = OFF (disabled).

Lock Value

12

or

Defines the four-digit code
required to enter Controller
Define Mode (and, if a common
lock code is used, Program
Define Mode).

0 to 9999.
Default = 10.

NOTES ON CONTROLLER DEFINE MODE PARAMETERS

1. The Process Variable Offset value should be chosen with care. Any adjustment to this parameter
is, in effect, a calibration adjustment. Injudicious application of values to this parameter could lead to
the displayed process variable value bearing no meaningful relationship to the actual process variable
value. There is no front panel indication when this parameter is in effect (i.e. has been set to a
non-zero value).

2. These parameters are applicable only if the secondary Control (COOL) ooutput is fitted.

3. These parameters are not applicable if Proportional Band 1 is set to 0 (i.e. ON/OFF control for
Output 1).

4. This parameter is not applicable if Proportional Band 1 is set to 0 or if Output 2 (COOL) is not fitted.

5. The Message Display will show Diff 1 for ON/OFF control on Output 1, Diff 2 for ON/OFF control
on Output 2 or Diff for ON/OFF control on both Output 1 and Output 2.

Page 9-5

59215-9