Configuration level

8840 profiler

33

Configuration parameters

InP.2

Name

Value range Description

Default

I.Fnc

Function selection of INP2

1

0

no function (subsequent input data are skipped)

1

heating current input

2

External set-point SP.E (switch-over -> LOGI/ SP.E)

3

Position feedback Yp

4

Second process value x2 (ratio, min, max, mean)

5

External positioning value Y.E

(switch-over r LOGI / Y.E)

6

no controller input (e.g. transmitter input instead)

7

Process value x1

S.tYP

Sensor type selection

30

30

0...20mA / 4...20mA 1

31

0...50mA AC 1

50

Potentiometer ( 0...160 Ohm) 1

51

Potentiometer ( 0...450 Ohm) 1

52

Potentiometer ( 0...1600 Ohm) 1

53

Potentiometer ( 0...4500 Ohm) 1

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at CAL level)

2

2-point correction (at CALlevel)

3

Scaling (at PArA level)

In.F

-1999...9999

Alternative value for error at INP2

OFF

fAI2

Forcing INP2 (only visible with 8800/8840 Configurator!)

0

0

No forcing

1

Forcing via serial interface

InP.3

Name

Value range Description

Default

I.Fnc

Function selection of INP3

1

0

no function (subsequent input data are skipped)

1

heating current input

2

External set-point SP.E (switch-over -> LOGI/ SP.E)

3

Yp input

4

Second process value X2

5

External positioning value Y.E

(switch-over r LOGI / Y.E)

6

no controller input (e.g. transmitter input instead)

7

Process value x1