2-point correction ( ConF/ InP.1 / Corr = 2):

InL.1: The input value of the lower scaling point is displayed.

The operator must adjust the lower input value by means of a

process value simulator and confirm the input value by pressing key Ù.

OuL.1: The display value of the lower scaling point is displayed.

Before calibration, OuL.1 equals InL.1.

The operator can correct the lower display value by pressing the ÈÌ

keys. Subsequently, he confirms the display value by pressing key Ù.

InH.1: The input value of the upper scaling point is displayed. .

The operator must adjust the upper input value by means of the

process value simulator and confirm the input value by pressing key Ù.

OuH.1: The display value of the upper scaling point is displayed.

Before calibration OuH.1 equals InH.1.

The operator can correct the upper display value by pressing keys ÈÌ

Subsequently, he confirms the display value by pressing key Ù.

g

The parameters (OuL.1, OuH.1) changed at CAL level can be reset by adjusting the

parameters below the lowest adjustment value (OFF) by means of decrement key Ì.

Calibration level