Configuration 40, Out.4, Out.5 – West Control Solutions N8840 User Manual

Page 40: Out.6, Logi

Advertising
background image

Configuration level

Configuration parameters

40

8840 profiler

Name

Value range Description

Default

CAll

Operator call

0

0

not active

1

active

Out.0

-1999...9999

Scaling of the analog output for 0% (0/4mA or 0/2V, only

visible when O.TYP=1..5)

0

Out.1

-1999...9999

Scaling of the analog output for 100% (20mA or 10V, only

visible when O.TYP=1..5)

100

O.Src

Signal source of the analog output OUT3 (only visible when

O.TYP=1..5)

1

0

not used

1

controller output y1 (continuous)

2

controller output y2 (continuous)

3

process value

4

effective set-point Weff

5

control deviation xw (process value - set-point)

6

measured value position feedback Yp

7

measured value INP1

8

measured value INP2

9

measured value INP3

fOut

Forcing OUT3 (only visible with 8800/8840 Configurator!)

0

0

No forcing

1

Forcing via serial interface

Out.4

Configuration parameters Out.4 as Out.3

Out.5

Configuration parameters Out.2 as Out.1 except for: Default Y.1 = 0 Y.2 = 0

Out.6

Configuration parameters Out.2 as Out.1 except for: Default Y.1 = 0 Y.2 = 0

g

Method of operation and usage of output Out.1 to Out.6:

Is more than one signal chosen active as source, those signals are OR-linked.

LOGI

Name

Value range Description

Default

L_r

Local / Remote switching (Remote: adjusting of all values

by front keys is blocked)

0

0

no function (switch-over via interface is possible)

1

always active

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches