5 8840 profiler cooling functions 48, 1 standard ( cycl= 0 ) 48, Constant period 48 – West Control Solutions N8840 User Manual

Page 48: Standard 48

Advertising
background image

4.5 8840 profiler cooling functions

With the 8840 profiler , configuration parameter CYCL (ConF/ Cntr/ CYCL)

can be used for matching the cycle time of 2-point and 3-point controllers. This

can be done using the following 4 methods.

4.5.1 Standard ( CyCl= 0 )

The adjusted cycle times t1 and t2 are valid for 50% or -50% correcting

variable. With very small or very high values, the effective cycle time is extended

to prevent unreasonably short on and off pulses. The shortest pulses result from

¼ x t1 or ¼ x t2. The characteristic curve is also called “bath tub curve”

Parameters to be adjusted: t1 : min. cycle time 1 (heating) [s]

( PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

4.5.2 Heating and cooling with constant period ( CyCl= 3 )

t1 and t2 are met in the overall

output range . To prevent

unreasonably short pulses, parameter

tp is used for adjusting the shortest

pulse duration. With small correcting

values which require a pulse shorter

than the value adjusted in tp, this

pulse is suppressed. However, the

controller stores the pulse and

totalizes further pulses, until a pulse

of duration tp can be output.

Parameters to be adjusted:

t1 : Min. cycle time 1 (heating) [s]

( PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

tp: min. pulse length [s]

Configuration level

8840 profiler cooling functions

48

8840 profiler

0,0

1,0

2,0

3,0

4,0

5,0

6,0

5

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95

Controller output [%]

relative

cycle

duration

T / T

1

t1

2 x t1

3 x t1

4 x t1

50%

50%

t1 t2

/

tp

tp

30%

70%

20%

80%

10%

90%

t1 t2

/

Advertising