Optimization at the setpoint 19 – West Control Solutions KS 50-1 User Manual

Page 19

Advertising
background image

Step attempt after start-up

Condition:

-

tunE = 0 and sufficient set-point reserve provided or

-

tunE = 2

The controller outputs 0% correcting variable or

Y.Lo and waits, until the process

is at rest (see start-conditions on page 8).
Subsequently, a correcting variable step change to 100% or

Y.Hi is output.

The controller attempts to calculate the optimum control parameters from the pro-
cess response. If this is done successfully, the optimized parameters are taken
over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% or
Y.Lo (100% cooling energy) is output from the set-point. After successfull deter-
mination of the “cooling parameters”, line-out to the set-point is using the optimi-
zed parameters.

Pulse attempt after start-up

Condition: -

tunE = 1 and sufficient set-point reserve provided.

The controller outputs 0% correcting variable or

Y.Lo and waits, until the process

is at rest (see start conditions page 8)
Subsequently, a short pulse of 100% or

Y.Hi is output (Y=100%) and reset.

The controller attempts to determine the optimum control parameters from the
process response. If this is completed successfully, these optimized parameters
are taken over and used for line-out to the set-point.

With a 3-point controller, this is followed by “cooling”.

After completing the 1st step as described and line-out to the set-point, correcting
variable "heating" remains unchanged and a cooling pulse (100% cooling energy)
is output additionally. After successful determination of the “cooling parame-
ters”, the optimized parameters are used for line-out to the set-point.

Optimization at the set-point

Conditions:

w

A sufficient set-point reserve is not provided at self-tuning start (see page 18).

w

tunE is 0 or 1

w

With

Strt = 1 configured and detection of a process value oscillation by

more than

± 0,5% of (rnG.H - rnG.L) by the controller, the control parame-

ters are preset for process stabilization and the controller realizes an optimiza-
tion at the set-point
(see figure “Optimization at the set-point”).

w

when the step attempt after power-on has failed

w

with active gradient function (

PArA/ SETP/ r.SP¹ OFF), the set-point

gradient is started from the process value and there isn't a sufficient set-point
reserve.

Operation

KS50/52-1

19

Self-tuning