Configuration 32, Out.1, Out.2 – West Control Solutions KS 50-1 User Manual

Page 32: Out.3, Configuration level

Advertising
background image

Name

Value range Description

Default

Hour

OFF..999999

Operating hours (only visible with BlueControl!)

OFF

Swit

OFF..999999

Output switching cycles (only visible with BlueControl!)

OFF

Out.1

Name

Value range Description

Default

O.Act

Method of operation of output OUT1

0

0

direct / normally open

1

inverse / normally closed

Y.1
Y.2

Controller output Y1/Y2

1

0

not active

1

active

Lim.1
Lim.2
Lim.3

Limit 1/2/3 signal

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP)

0

0

not active

1

active

HC.AL

Heat current alarm signal

0

0

not active

1

active

HC.SC

Solid state relay (SSR) short circuit signal

0

0

not active

1

active

P.End

Programmer end signal

0

0

not active

1

active

FAi.1
FAi.2

INP1/ INP2 error signal

0

0

not active

1

active

fOut

Forcing OUT1 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

Out.2

Configuration parameters

Out.2 as Out.1 except for: Default Y.1 = 0, Y.2 = 1

Out.3

Name

Value range Description

Default

O.tYP

Signal type selection OUT3

0

0

relay / logic (only visible with current/logic voltage)

1

0 ... 20 mA continuous (only visible with current/logic/voltage)

2

4 ... 20 mA continuous (only visible with current/logic/voltage)

3

0...10 V continuous (only visible with current/logic/voltage)

4

2...10 V continuous (only visible with current/logic/voltage)

Configuration level

Configurations

32

KS50/52-1