4.3 Set-point processing

The set-point processing structure is shown in the following picture:

4.3.1

Set-point gradient / ramp

To prevent set-point step changes, parameter r set-point r r.SP can be adjusted to
a maximum rate of change. This gradientis effective in positive and negative di-
rection..

With parameter

r.SP set to OFF (default), the gradient is switched off and

set-point changes are realized directly.

(for parameter: see page )

4.4 KS50-1 cooling functions

With KS50-1, configuration parameter

CYCL (ConF/ Cntr/ CYCL) can be

used for matching the cycle time of 2-point and 3-point controllers. This can be
done using the following 4 methods.

4.4.1

Standard (

CyCl= 0 )

The adjusted cycle times

t1 and t2 are valid for 50% or -50% correcting varia-

ble. With very small or very high values, the effective cycle time is extended to

Configuration level

Set-point processing

38

KS50/52-1

10

1

0

Ü

Xeff

SP.2

SP.E

0/4...20 mA

internal
set-point

*

Ö

125

126

SP.x

run

Err

Ada

SP.Hi

SP.Lo

r.SP

- LED

external
set-point
INP2

Limitation

Ramp

2.set-point

effective
set-point

ù

Programmer

Start-up circuit

Boost

Index:

Ь
*
Ц

: int/ext-setpoint switching
: configuration
:

/

switching

SP.Fn

SP SP.2

The ramp starts at process value
with the following switchings:

- int / ext-setpoint switching
-

/

switching

- Manual-/ Automatic switching
- at power on

SP SP.2