8.3 KS50/52-1 as Modbus master

a

This function is only selectable with BlueControl (engineering tool)!

Additions

othr

(only visible with BlueControl!)

Name

Value range Description

Default

MASt

Controller is used as Modbus master

0

0

Slave

1

Master

Cycl

0...200

Cycle time [ms] for the Modbus master to transmit its data to the

bus.

60

AdrO

1...65535

Target address to which the with

AdrU

specified data is given out on

the bus.

1

AdrU

1...65535

Modbus address of the data that Modbus master gives to the bus.

1

Numb

0...100

Number of data that should be transmitted by the Modbus

master.

0

The controller can be used as Modbus master (

ConF / othr / MASt = 1 ).

The Modbus master sends ist data to all slaves (broadcast message, controller
adress 0). It transmits its data (modbus adress AdrU) cyclic with the cycle time
Cycl to the bus. The slave controller receives the data transmitted by the masters
and allocates it to the modbus target adress AdrO.

If more than one data should be transmitted by the master controller ( Numb >

1)

, the modbus adress AdrU indicates the start adress of the data that should be
transmitted and AdrO indicates the first target adress where the received data
should be stored. The following data will be stored at the logically following
modbus target adresses.

With this it is possible e.g. to specify the process value of the master controller as
set-point for the slave controllers.

Special functions

KS50/52-1 as Modbus master