Technical data

TB40-1

27

Range

Input resistance

Accuracy

Resolution (Ô)

0-10 Volt

~ 110 kW

Я 0,1 %

Я 0,6 mV

0-20 mA

49

W (voltage requirement ß 2,5 V)

Я 0,1 %

Я 1,5 mA

Table 3 Current and voltage measuring ranges

Type

Sens. current

Range

Accuracy

Resolution (Ô)

Pt100

0,2mA

-200...100°C

-140...212°F

ß 1K

0,1K

Pt100

-200...850°C

-140...1562°F

ß 1K

0,1K

Pt1000

-200...850°C

-140...392°F

ß 2K

0,1K

KTY 11-6 *

-50...150°C

-58...302°F

ß 2K

0,05K

* Or special

Table 2 Resistance transducer measuring ranges

Type

Range

Accuracy

Resolution (Ô)

L

Fe-CuNi (DIN)

-100...900°C

-148...1652°F

ß 2K

0,1 K

J

Fe-CuNi

-100...1200°C

-148...2192°F

ß 2K

0,1 K

K

NiCr-Ni

-100...1350°C

-148...2462°F

ß 2K

0,2 K

N

Nicrosil/Nisil

-100...1300°C

-148...2372°F

ß 2K

0,2 K

S

PtRh-Pt 10%

0...1760°C

32...3200°F

ß 2K

0,2 K

R

PtRh-Pt 13%

0...1760°C

32...3200°F

ß 2K

0,2 K

T

Cu-CuNi

-200...400°C

-328...752°F

ß 2K

0,05 K

C

W5%Re-W26%Re

0...2315°C

32...4199°F

ß 2K

0,4 K

D

W3%Re-W25%Re

0...2315°C

32...4199°F

ß 2K

0,4 K

E

NiCr-CuNi

-100...1000°C

-148...1832°F

ß 2K

0,1 K

B *

PtRh-Pt6%

0(100)...1820°C

32(212)...3308°F

ß 2K

0,3 K

* Specifications valid from 400°C

Table 1 Thermocouple measuring ranges