2 electrical connections 5, 1 connecting diagram 5, 2 terminal connection 5 – West Control Solutions TB 40-1 Temperature Monitor User Manual

Page 5: Connecting diagramm 5, 90 v 24v ac/dc, Ab c d, 2electrical connections 2.1 connecting diagram, 2 terminal connection

Advertising
background image

2

Electrical connections

2.1 Connecting diagram

*

Safety switch mA i V in position left

g

The controller is fitted with flat-pin terminals 1 x 6,3mm or 2 x 2,8mm
to DIN 46 244 or screw terminals from 0,5 to 2,5mm².

2.2 Terminal connection

Power supply connection

1

See chapter

"Technical data"

Connection of input INP1

2

Input for variable x1 (process value)
a

thermocouple

b

resistance thermometer (Pt100/ Pt1000/ KTY/ ...)

c

current (0/4...20mA)

d

voltage (0/2...10V)

Electrical connections

TB40-1

5

Connecting diagram

L
N

90...250V

24V AC/DC

mA

0..10 V*

di1

INP1

LC

OUT2

OUT1

1

2

3

4

7

5

8

6

9

10

11

12

13

14

15

a

b

c

d

Additional
alarms

Advertising