6 limit value processing 26, Limit values 26 - 27, Limit value processing – West Control Solutions TB 45 Temperature Monitor User Manual

Page 26: Üû/o

Advertising
background image

g

With O

2

measurement, specification if parameters related to the measured value should be output in ppm

or % is required. This is done centrally during configuration.

othrr O2

0

unit: ppm

1

unit: %

g

Whether the temperature of the non-heated

l probe is entered in °C, °F or K can be selected during

configuration.

othrr Unit

1

°C

2

°F

3

K

Displays

With configuration for O

2

measurement (see above), the oxygen content is dis-

played as process value with the selected unit (see above) on line 1. Max. 4 char-
acters can be displayed.

With display range overflow, “

EEEE” is displayed .

Example: the ppm range is selected, but the value is a % value.
When exceeding the display span start, 0 is displayed.

+

Tip: the unit can be displayed on line 2.

6.6

Limit value processing

The main alarm acts on the process value and is firmly allocated to relay output LC the output action of which is set to
inverse continuously. With the temperature monitor function, the limit value is adjusted by means of parameter LC.
With the limit signaller function, the limit value is adjusted via

L.1 / H.1. The limit value switching difference

HYS.1 is adjustable.

Max. two further limit values can be configured as pre-alarms and allocated to the individual outputs

Out.2....

Out.3.
Several signals assigned to an output are logically ORed.

g

The signal to be monitored can be selected separately for each alarm via configuration. The following
signals are available:

Main alarm LC

Process value (display value)

Pre-alarms Lim.2 / Lim.3

Process value (display value)

Measured value INP1

Measured value INP2 (optional)

Functions

26

Limit value processing

TB 45

20.95

üû/o