9 reset to default 32, Reset to default – West Control Solutions TB 45 Temperature Monitor User Manual

Page 32

Advertising
background image

g

When an alarm is still pending, i.e. unless the error cause was removed (E display blinks), latched alarms
cannot be acknowledged and reset.

6.9

Reset to default

In case of faulty configuration, the device can be
reset to the default manufacturers condition.

1

For this, the operator must keep the keys
increment and decrement pressed during
power-on.

2

Then, press key increment to select

YES

.

3

Press enter to call up the password menu and
to enter the valid password. If the password
is faulty, reset is not possible.

4

Confirm factory resetting with Enter and the
copy procedure is started
(display

COPY

).

5

Afterwards the device restarts.

In all other cases, no reset will occur (timeout
abortion).

g

If one of the operating levels was blocked in
BlueControl

Ò

, reset to factory setting is not

possible.

g

The copy procedure (

COPY

) can take

some seconds.

g

Now, the transmitter is in normal operation.

Functions

32

Reset to default

TB 45

FAC

torY

FAC

no

+ Power on

FAC

yEs

ô

FAC

PASS

8.8.8.8

#:#:#:#:#

дддд

1

2

3

4

5

FAC

COPY