I/O connection

(Function no.: 2)

Code Des.

R/W Type

Description

Range

Rem.

0

Block 1...2

R

Block

1

State_alarm_out R

ST1

Status alarm outputs

G

2

State_dio

R

ST1

Status digital inputs/outputs

H

20

Block 21...24

L

Block

21

SnOEMOpt

L

INT

Seriennummer OEM-Feld

22

SnFabMonth

L

INT

Seriennummer Fabrikationsmonat

23

SnCntHi

L

INT

Seriennummer Zähler High

24

SncntLo

L

INT

Seriennummer Zähler Low

30

Block 31...33

L

Block

31

Fdo1

L/S ICMP Forced digitale Ausgänge: OUT1 ... OUT8

J

32

Fdo2

L/S ICMP Forced digitale Ausgänge: OUT9 ... OUT16

K

33

Fdo3

L/S ICMP Forced digitale Ausgänge: OUT17 ... OUT19

L

Bem. H State_alarm_out

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

R1

Relay 1

off

on

D1

R2

Relay 2

off

on

D2

R3

Relay 3

off

on

D3

do1_12 AL

Alarm output short circuit do1 ... do12

off

on

D4

HCscAL

Alarm message heating current short circuit off

on

D5

‘0’

Always ‘0’

D6

‘1’

Always ‘1’

D7

Parity

Bem. I State_dio

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no. Name

Allocation

Status ‘0’

Status ‘1’

D0

Par_Nr

Parameter set number

set 0

set 1

D1

w/w2

w/w2 switch-over

w

w2

D2

Coff

Controller off

off

on

D3

Leck

Leakage current

off

on

D4

‘0’

Always ‘0’

D5

do13_16f

do13 ... do16 Fail

no

yes

D6

‘1’

Always ‘1’

D7

Parity

Bem. J Aufbau der Datenstruktur

Bit

15 14 13 12 11 10 9 8

7

6

5

4

3

2

1

0

Bedeutung 0 0 0 0 0 0 0 0 OUT8 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1

Bem. K Aufbau der Datenstruktur

Bit

15 14 13 12 11 10 9 8

7

6

5

4

3

2

1

0

Bedeutung 0 0 0 0 0

0 0 0 OUT16 OUT15 OUT14 OUT13 OUT12 OUT11 OUT10 OUT9

Bem. L Aufbau der Datenstruktur

Bit

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Bedeutung

0

0

0

0

0

0

0

0

0

0

0

0

0

OUT19 OUT18 OUT17

Function block protocol