2 basic message structure 9, Function block number 9, Function number 9 – West Control Solutions KS 800 ISO1745 Interface Manual User Manual

Page 9: Safety procedure 9, Basic message structure

Advertising
background image

Bem. E Addition selection criteria

In order to form a purposeful sub-set from the variety of data, additional selection criteria are defined:

q

Function block number

A function block is addressed by a function block number. It is within ‘0’ and ‘250’ and is appended to

the code field by means of a comma.‘<code>,<function block no.>’

Function block number ranges:

w

0general data for the overall instrument

w

1 - 99fixed function blocks

w

100 - 250variable function blocks

q

Function number

A function as a partial address of a function block is addressed with a function number. It is within ‘0’

and ‘99’ and is appended to the function block number by means of a comma.

‘<code>,<function block no.>,<function no.>’

Function number ranges:

w

0 - 99Functions

w

0Function General, Default, unless a no. is specified

Bem. F Safety procedure

Correct transmission of a message is supported by two safety procedures:

w

check of each message byte by formation of parity (1 bit per 7 data bits)

w

Check by Block Check Count : safety section, which connects all characters of a message between STX

(excl.) and ETX (incl.) bytewisely by a logic XOR function; length 1 byte, follows always after ETX.

3.2

Basic message structure

Message structure with data transmission:

Computer sends

to KS 800:

EOT

STX

ETX BCC

<addr>

<data>

KS 800 replies:

ACK

or

NAK in case of error

Message structure with data enquiry:

Computer requests:

EOT

ENQ

<addr>

<ident>

KS 800 replies:

STX

ETX

BCC

or

NAK in case of error

<data>

Message structure

9

9499 040 49411