1 transmission control characters 7, 2 character format 7, Character format 7 – West Control Solutions KS 800 ISO1745 Interface Manual User Manual

Page 7: Data request 7, Transmission control characters 7, 1 transmission control characters, 2 character format

Advertising
background image

q

for data request: RDR (Request Data with Reply)

data request with reply in one message cycle.

Data flow direction : KS800 r Master

a) Master

EOT <address> <identification> ENQ

b)

KS800

STX <data> ETX BCC

NAK

1)

no reaction

2)

c) Master

EOT

or continue with a

repeat a,

or EOT

(1)

after timeout:

EOT or continue with a

(2)

2.2.1

Transmission control characters

The following transmission control characters are used:

Abbreviation

HEX

Description

STX

02

Start of Text - data introduction

ETX

03

End of Text - end of data

EOT

04

End of Transmission - reset the interface units or transmission cancelation

ENQ

05

Enquiry - request for reply

ACK

06

Acknowledge - confirmation

NAK

15

Not Acknowledge - no confirmation

2.2.2

Character format

Numbers and characters in the address, identification or data field are always transmitted as ASCII

characters.

The following 7-bit ASCII characters with parity (EVEN) are valid

CHR

HEX

Description

,

2C

Comma as separator

=

3D

Separator between identification and value

0...9

30...39 Values for numbers and codes

B

41

Additional for codes

:...?

3A...3F Values for floating point format (FP)

@...

40...7F Values for status and control bytes

...

20...7F Characters for text string (CHAR16)

.

2E

Decimal point

Interface protocol

7

9499 040 49411

1) Possible after disturbance of transmission or after sending inadmissible data.

2) Possible after KS 800 failure, bus failare or faulty address specification.

Advertising