Electrical Data Free Cool Chiller Extra Quiet

ELECTRICAL DATA

DCF017SX-04AM00

DCF021SX-06BS00

DCF025SX-06BT00

Unit Data

Nominal Run Amps

(1)

A

105.0

144.2

157.5

Maximum Start Amps

A

377.5

318.1

382.5

Recommended Mains Fuse Size

A

125

200

200

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

6

6

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

4

6

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5

43.1

47.5

Quantity

2

3

3

Motor Rating

kW

28.2

24.0

28.2

Sump Heater Rating

W

130

75

130

Start Amps

A

320

260

320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

36.5

42.8

Circuit 2 Comp RLA (PFC)

N/A

N/A

N/A

Nominal Run Amps

A

95.6

124.5

143.4

Maximum Start Amps

A

372.8

311.5

377.8

Compressor Nominal Run Amps

A

42.8

36.5

42.8

Recommended Mains Fuse Size

A

125

160

200

Electronic Soft-start

Nominal Run Amps

A

105.0

144.2

157.5

Maximum Start Amps

A

249.5

257.1

302.0

Recommended Mains Fuse

A

125.0

200.0

200.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

95.6

124.5

143.4

Maximum Start Amps

A

244.8

244.0

292.6

Compressor Nominal Run Amps

A

42.8

36.5

42.8

Recommended Mains Fuse Size

A

125

160

200

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

N/A

N/A

N/A

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

113.9

153.1

166.4

Recommended Mains Fuse Size

A

160

200

200

Motor Rating

kW

4

4

4

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.8

11.8

11.8

Unit Nominal Run Amps

A

116.8

156.0

169.3

Recommended Mains Fuse Size

A

160

200

200

Motor Rating

kW

5.5

5.5

5.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

8

11.2

Unit Nominal Run Amps

A

111.3

152.2

168.7

Recommended Mains Fuse Size

A

160

200

200

Motor Rating

kW

3

4

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

11.2

14.8

Unit Nominal Run Amps

A

113.0

155.4

172.3

Recommended Mains Fuse Size

A

160

200

200

Motor Rating

kW

4

5.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.