Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC022DR-06AKK0

DCC024DR-04BKL0

DCC025DR-06BKL0

Unit Data

Nominal Run Amps

(1)

A

157.9

169.4

178.0

Maximum Start Amps

(2)

A

339.9

386.3

394.9

Recommended Mains Fuse Size

A

200

200

200

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

4

6

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

6

4

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 33.0

43.1 / 33.0

43.1 / 33.0

Quantity

2 + 2

2 + 2

2 + 2

Motor Rating

kW

18.8 / 18.8

24.0 / 18.8

24.0 / 18.8

Sump Heater Rating

W

75

75

75

Start Amps (2)

A

215 / 215

260 / 215

260 / 215

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

36.5

36.5

Circuit 2 Comp RLA (PFC)

28.5

28.5

28.5

Nominal Run Amps

A

139.8

147.2

155.8

Maximum Start Amps

A

326.3

370.7

379.3

Compressor Nominal Run Amps

A

28.5 / 28.5

36.5 / 28.5

36.5 / 28.5

Recommended Mains Fuse Size

A

200

200

200

Electronic Soft-start

Nominal Run Amps

A

157.9

169.4

178.0

Maximum Start Amps

A

253.9

282.3

290.9

Recommended Mains Fuse

A

200

200

200

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

139.8

147.2

155.8

Maximum Start Amps

A

240.3

266.7

275.3

Compressor Nominal Run Amps

A

28.5 / 28.5

36.5 / 28.5

36.5 / 28.5

Recommended Mains Fuse Size

A

200

200

200

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.2

6.2

6.2

Unit Nominal Run Amps

A

164.1

175.6

184.2

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

3

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

166.8

178.3

186.9

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

4

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

8.0

8.0

Unit Nominal Run Amps

A

164.2

177.4

186.0

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

3

4

4

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

11.2

11.2

Unit Nominal Run Amps

A

165.9

180.6

189.2

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

4

5.5

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.