Technical Manual :7022932_V1.9_11/2013

Hydronic Data


Waterside Pressure Drops

CAUTION

Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty.

Use the formula below to calculate the External Head Available:

Total Pump Head Available

-

Chiller Pressure Drop

=

External Head Available

Example: DCC033DR-08BMH0

Water flow : 15.6 l/s

Pump Option : 6

Chiller Pressure Drop : 39.6 kPa

Total Pump Head Available : 182 kPa

182 kPa

-

39.6 kPa

=

142.4 kPa

Pum

p

Ava

ila

bl

e

He

a

d

(

k

Pa

)

0

50

100

150

200

250

300

350

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

4

5

6

7

Water flow (l/s)

1

Chiller pressure drop refers to standard unit only. For pump options, please contact Airedale.

2

For glycol solutions, please refer to

Glycol Data

, on page 24.

NOTE

To determine a flow rate from the available external head; adjust the flow until the unit
pressure matches the total head available (from the pump curve minus the pressure
drop of the unit). Checks can be made on the evaporator pressure drop to ensure
correct operation.