Electrical data extra quiet, Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 75
Chillers
DELTACHILL
™
Chillers
75
Technical Manual :7022932_V1.9_11/2013
Electrical Data Extra Quiet
ELECTRICAL DATA
DCC011SX-04AK00
DCC014SX-04AL00
DCC017SX-04AM00
Unit Data
Nominal Run Amps
(1)
A
76.0
96.1
105.0
Maximum Start Amps
(2)
A
258.0
313.1
377.5
Recommended Mains Fuse Size
A
100
125
125
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
33.0
43.1
47.5
Quantity
2
2
2
Motor Rating
kW
18.8
24.0
28.2
Sump Heater Rating
W
75
75
130
Start Amps (2)
A
215
260
320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
28.5
36.5
42.8
Circuit 2 Comp RLA (PFC)
N/A
N/A
N/A
Nominal Run Amps
A
67.0
83.0
95.6
Maximum Start Amps
A
253.5
306.5
372.8
Compressor Nominal Run Amps
A
28.5
36.5
42.8
Recommended Mains Fuse Size
A
100
125
125
Electronic Soft-start
Nominal Run Amps
A
76.0
96.1
105.0
Maximum Start Amps
A
172.0
209.1
249.5
Recommended Mains Fuse
A
100
125
125
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
67.0
83.0
95.6
Maximum Start Amps
A
167.5
202.5
244.8
Compressor Nominal Run Amps
A
28.51
36.48
42.78
Recommended Mains Fuse Size
A
100
125
125
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
81.0
101.1
110.0
Recommended Mains Fuse Size
A
100
125
160
Motor Rating
kW
2.2
2.2
2.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
6.6
Unit Nominal Run Amps
A
81.0
101.1
111.6
Recommended Mains Fuse Size
A
100
125
160
Motor Rating
kW
2.2
2.2
3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
4.5
4.5
4.5
Unit Nominal Run Amps
A
80.5
100.6
109.4
Recommended Mains Fuse Size
A
100
125
160
Motor Rating
kW
2.2
2.2
2.2
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
6.3
Unit Nominal Run Amps
A
82.3
102.4
111.3
Recommended Mains Fuse Size
A
100
125
160
Motor Rating
kW
3
3
3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.