Electrical Data Extra Quiet

ELECTRICAL DATA

DCC011SX-04AK00

DCC014SX-04AL00

DCC017SX-04AM00

Unit Data

Nominal Run Amps

(1)

A

76.0

96.1

105.0

Maximum Start Amps

(2)

A

258.0

313.1

377.5

Recommended Mains Fuse Size

A

100

125

125

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

4

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

4

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0

43.1

47.5

Quantity

2

2

2

Motor Rating

kW

18.8

24.0

28.2

Sump Heater Rating

W

75

75

130

Start Amps (2)

A

215

260

320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

36.5

42.8

Circuit 2 Comp RLA (PFC)

N/A

N/A

N/A

Nominal Run Amps

A

67.0

83.0

95.6

Maximum Start Amps

A

253.5

306.5

372.8

Compressor Nominal Run Amps

A

28.5

36.5

42.8

Recommended Mains Fuse Size

A

100

125

125

Electronic Soft-start

Nominal Run Amps

A

76.0

96.1

105.0

Maximum Start Amps

A

172.0

209.1

249.5

Recommended Mains Fuse

A

100

125

125

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

67.0

83.0

95.6

Maximum Start Amps

A

167.5

202.5

244.8

Compressor Nominal Run Amps

A

28.51

36.48

42.78

Recommended Mains Fuse Size

A

100

125

125

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

5

Unit Nominal Run Amps

A

81.0

101.1

110.0

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

6.6

Unit Nominal Run Amps

A

81.0

101.1

111.6

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

2.2

2.2

3

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

4.5

4.5

Unit Nominal Run Amps

A

80.5

100.6

109.4

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

6.3

Unit Nominal Run Amps

A

82.3

102.4

111.3

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

3

3

3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.