FUTEK IPM52x (D520) Digital Display User Manual

Page 23

Advertising
background image

22

2.

Alarm one is different from one standpoint. It has

the additional selection of "SAFE"(fail safe)

selection. The selection "SAFE" here controls

relays 1 through 3 for the fail-safe operation.

b.

"CHANEL"

selects which channel alarm is being assigned to.

Use

SELECT key to view choice of channels. Use ENTER key

to enter choice.

c.

"RELAY" selects which relay (1 through 4) is being

programmed. Use

SELECT key to view choices of outputs. Use

the

ENTER key to enter choice.

NOTE: Relays 1 through 3 are optional and located on the

option/top board. Relay 4 is standard and located on the

main/bottom board.

d.

"TYPE" selects what type of alarm. Use

SELECT key to view

following choices. Use the

ENTER key to enter choice.

1.

"ALAR HI" (alarm high) selects alarm to trigger when

input goes over programmed set point.

2.

"ALAR LO" (alarm low) selects alarm to trigger when

input goes under programmed set point.

e.

"SET PT" (set point) enter number at which alarm will occur.

Set point can also be programmed from the RUN mode when

an

F key is assigned to display alarm. If F key is held for 4

seconds, the display will start flashing the right hand digit

signifying the new set point can be entered.

Note: The corresponding front panel alarm LED is on when

in alarm.

Note: Alarm set point can only be changed enabled on the

alarm setup menu, otherwise you can only view the set point.

f.

"HYST" (hysteresis / deadband) enter number. This number is

added to a low limit or subtracted from a high limit before an

alarm condition is cancel. It is typically used to prevent alarm

chatter.

g.

"LATCH" selects alarm to latching or non-latching (follows

input). If LATCHING is selected, alarm will remain on till

manually reset. Use

SELECT key to view “YES” for latching