* AWG Stranded Type Wire ... for individual lengths less than 100 feet.

(Motor lead type wire is recommended)

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the back of the dryer, at the upper right hand corner. In the case of
208 VAC or 240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.

WARNING: 208 VAC and 240 Volts ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or

obligation.

ADE-120ES (72 Kw Electric) Reversing, 3ø

E

LECTRICAL

S

ERVICE

S

PECIFICATIONS

(

PER DRYER

)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES:

A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to

appliance amp draw rating and type of breaker used.

C. Circuit breakers for 3Ø dryers must be 3-pole type.

OVEN SIZE

((Kw)

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE*

FUSING

CIRCUIT

BREAKER

Dual Element

Time Delay

60 Hz

50 Hz

72

208

3

214

---

4/0

300

300

72

240

3

186

187

3/0

250

250

72

380

3

117

117

1

150

150

72

380

4

117

117

1

150

150

72

416

3

---

107

2

150

150

72

416

4

---

107

2

150

150

72

480

3

98

---

3

150

125

72

480

4

98

---

3

150

125

72

575/600

3/4

79.4

---

4

100

110