Figure 3. sensor cabling option a – ADC P-80-412 User Manual

Page 5

Advertising
background image

ADCP-80-412

N Issue 1 N April 2000

Page 5

© 2000, ADC Telecommunications, Inc.

a.

Unsnap the top bar of the inductive pick-up coil. Insert the main DSX-1 or DSX-3
–48 Vdc power conductor into the inductive pick-up coil as shown in

Figure 3

, making

sure that the label side of the coil faces toward the power source. Snap the top bar back
into place after inserting the power feed wire. Anchor the power conductor to the
inductive pick-up coil with a tie wrap or lacing cord in accordance with local practice.

b.

Unsnap the top bar of the inductive pick-up coil. Insert the –48 Vdc conductors for the
DSX-only equipment into the inductive pick-up coil as shown in

Figure 4

, making sure

that the label side of the coil faces toward the power source. Snap the top bar back into
place after inserting the power feed wire(s). Anchor the power conductor(s) to the
inductive pick-up coil with a tie wrap or lacing cord in accordance with local practice.

Note

: The battery return main conductor, or battery return distribution conductors are not

inserted into the coil and should be routed directly to the DSX-1 or DSX-3 fuse panel.

FILLER

PANEL

SENSOR

ATTACHMENT

INDUCTION

COIL

UPPER CABLE TROUGH

POWER

ATTACHMENT

BAYTRACER

FILLER

PANEL

—48V

—48V

BATTERY

RETURN

BATTERY

RETURN

FUSE PANEL

DSX

PANEL

DSX

PANEL

BATTERY RETURN

—48V

BATTERY RETURN

—48V

REAR VIEW

NOTE: SENSOR AND POWER ATTACHMENT POSITION AND
APPEARANCE SHOWN EXAGGERATED FOR CLARITY.

14088-A